CH80H — front
Analog Meter Relays
CH80H Analog Meter Relay (High Limit)
The black pointer shows the real-time value; the red needle is set by hand to the upper limit. When the black pointer rises above the limit, the internal relay switches at once and controls the external circuit.
Specifications
| Front frame | 80 × 80 mm |
|---|---|
| Set point | Single high limit (red needle) |
| Accuracy | AC: ±2.5% of full scale; DC: ±1.5% of full scale |
| Movement | Rectified moving-coil, high-damping magnet |
| Switching differential | Within 1% of the pointer indication; ON/OFF action error within 0.5% of full scale |
| Output relay | 3 A per contact set, AC 110/220 V |
| Power supply | AC 108–132 V or AC 210–230 V, 50–60 Hz (DC 24 V / DC 12 V also listed in the model table — Ask us) |
| Mechanical life | 200,000 operations |
Source: factory catalogue p.5. CH80H named on UDEM attestation M.2024.206.C99480.
Ranges
Measuring ranges — CH80H
| Measurement | Unit / connection | Standard ranges |
|---|---|---|
| AC current | mA | 500mA, 600mA, 800mA |
| A | 1A, 5A, 10A | |
| With external CT x/1A | 10/1A, 15/1A, 20/1A, 30/1A, 40/1A, 50/1A, 60/1A, 75/1A, 100/1A, 150/1A, 200/1A, 250/1A, 300/1A, 400/1A, 500/1A, 600/1A, 800/1A, 1000/1A, 1200/1A, 1500/1A, 2000/1A, 2500/1A, 3000/1A | |
| With external CT x/5A | 10/5A, 15/5A, 20/5A, 30/5A, 40/5A, 50/5A, 60/5A, 75/5A, 100/5A, 150/5A, 200/5A, 250/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A, 1200/5A, 1500/5A, 2000/5A, 2500/5A, 3000/5A | |
| AC voltage | V | 10V, 25V, 40V, 60V, 100V, 150V, 250V, 300V, 450V, 500V, 600V |
| kV | With an external PT: X/100V, X/110V, X/120V | |
| DC current | mA | 1mA, 10mA, 500mA, 800mA |
| A | 1A, 1.5A, 2A, 3A, 4A, 5A, 10A | |
| External shunt 50 / 60 / 75 mV | 10A, 15A, 20A, 30A, 40A, 50A, 60A, 100A, 150A, 200A, 250A, 300A, 400A, 500A, 600A, 800A, 1000A, 1500A, 2000A, 2500A, 3000A | |
| DC voltage | V | 0.5V, 1V, 5V, 10V, 25V, 50V, 100V, 250V, 500V, 600V |
Source: factory catalogue p.5. Other ranges and dual scales — ask us.
Drawings
Dimensions & drawings

Advantages
- Limits are set directly on the dial — no menus or keypads
- Reliable relay switching with a direct, at-a-glance reading
- Shows the dynamic trend of the parameter, not just a number
Applications
- Multi-station cold heading machines
- Automatic testing equipment
Ask us
- Samples and lead time — confirmed with each quote
- Custom scale, dial text or pointer — see custom dials
Request a quote
Quote for CH80H
Tell us AC or DC, the range or CT / shunt ratio, any dial changes and the quantity. Attach a photo or drawing of the meter you replace if you have one.
Need to compare first? Model selection guide · Request the attestation