RUFTEElectric
CH80H analog meter relay front view, AC current via C.T. 100/5 A

CH80H — front

Analog Meter Relays

CH80H Analog Meter Relay (High Limit)

The black pointer shows the real-time value; the red needle is set by hand to the upper limit. When the black pointer rises above the limit, the internal relay switches at once and controls the external circuit.

Specifications

Front frame80 × 80 mm
Set pointSingle high limit (red needle)
AccuracyAC: ±2.5% of full scale; DC: ±1.5% of full scale
MovementRectified moving-coil, high-damping magnet
Switching differentialWithin 1% of the pointer indication; ON/OFF action error within 0.5% of full scale
Output relay3 A per contact set, AC 110/220 V
Power supplyAC 108–132 V or AC 210–230 V, 50–60 Hz (DC 24 V / DC 12 V also listed in the model table — Ask us)
Mechanical life200,000 operations

Source: factory catalogue p.5. CH80H named on UDEM attestation M.2024.206.C99480.

Ranges

Measuring ranges — CH80H

MeasurementUnit / connectionStandard ranges
AC currentmA500mA, 600mA, 800mA
A1A, 5A, 10A
With external CT x/1A10/1A, 15/1A, 20/1A, 30/1A, 40/1A, 50/1A, 60/1A, 75/1A, 100/1A, 150/1A, 200/1A, 250/1A, 300/1A, 400/1A, 500/1A, 600/1A, 800/1A, 1000/1A, 1200/1A, 1500/1A, 2000/1A, 2500/1A, 3000/1A
With external CT x/5A10/5A, 15/5A, 20/5A, 30/5A, 40/5A, 50/5A, 60/5A, 75/5A, 100/5A, 150/5A, 200/5A, 250/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A, 1200/5A, 1500/5A, 2000/5A, 2500/5A, 3000/5A
AC voltageV10V, 25V, 40V, 60V, 100V, 150V, 250V, 300V, 450V, 500V, 600V
kVWith an external PT: X/100V, X/110V, X/120V
DC currentmA1mA, 10mA, 500mA, 800mA
A1A, 1.5A, 2A, 3A, 4A, 5A, 10A
External shunt 50 / 60 / 75 mV10A, 15A, 20A, 30A, 40A, 50A, 60A, 100A, 150A, 200A, 250A, 300A, 400A, 500A, 600A, 800A, 1000A, 1500A, 2000A, 2500A, 3000A
DC voltageV0.5V, 1V, 5V, 10V, 25V, 50V, 100V, 250V, 500V, 600V

Source: factory catalogue p.5. Other ranges and dual scales — ask us.

Drawings

Dimensions & drawings

CH80H dimensional drawing
CH80H dimensional drawing

Advantages

  • Limits are set directly on the dial — no menus or keypads
  • Reliable relay switching with a direct, at-a-glance reading
  • Shows the dynamic trend of the parameter, not just a number

Applications

  • Multi-station cold heading machines
  • Automatic testing equipment

Ask us

  • Samples and lead time — confirmed with each quote
  • Custom scale, dial text or pointer — see custom dials

Request a quote

Quote for CH80H

Tell us AC or DC, the range or CT / shunt ratio, any dial changes and the quantity. Attach a photo or drawing of the meter you replace if you have one.

More analog meter relays

Compare all
Request a QuoteWhatsApp