RUFTEElectric
CH120HL analog meter relay with high and low set pointers, DC 5 A scale

CH120HL — high and low set pointers

Analog Meter Relays

CH120H / CH120HL Analog Meter Relay

The black pointer shows the real-time value. The red and green needles are set by hand to the upper and lower limits. When the black pointer goes below the low limit or above the high limit, the internal relay switches at once and controls the external circuit.

Specifications

Front frame120 × 100 mm
AccuracyAC: ±2.5% of full scale; DC: ±1.5% of full scale
MovementRectified moving-coil, high-damping magnet
Set-point adjustmentSingle high limit: 0–100% of scale. High/low: low limit 0–95%, high limit 5–100% of scale, two set needles, minimum spacing 2°
Switching differentialWithin 1% of the pointer indication; ON/OFF action error within 0.5% of full scale
Output relay3 A per contact set, AC 110/220 V
Power supplyAC 108–132 V or AC 210–230 V, 50–60 Hz (DC 24 V / DC 12 V also listed in the model table — Ask us)
Mechanical life200,000 operations

Source: factory catalogue p.3, 5. CH120H, CH120HL named on UDEM attestation M.2024.206.C99480.

Ranges

Measuring ranges — CH120H / CH120HL

MeasurementUnit / connectionStandard ranges
AC currentmA500mA, 600mA, 800mA
A1A, 5A, 10A
With external CT x/1A10/1A, 15/1A, 20/1A, 30/1A, 40/1A, 50/1A, 60/1A, 75/1A, 100/1A, 150/1A, 200/1A, 250/1A, 300/1A, 400/1A, 500/1A, 600/1A, 800/1A, 1000/1A, 1200/1A, 1500/1A, 2000/1A, 2500/1A, 3000/1A
With external CT x/5A10/5A, 15/5A, 20/5A, 30/5A, 40/5A, 50/5A, 60/5A, 75/5A, 100/5A, 150/5A, 200/5A, 250/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A, 1200/5A, 1500/5A, 2000/5A, 2500/5A, 3000/5A
AC voltageV10V, 25V, 40V, 60V, 100V, 150V, 250V, 300V, 450V, 500V, 600V
kVWith an external PT: X/100V, X/110V, X/120V
DC currentmA1mA, 10mA, 500mA, 800mA
A1A, 1.5A, 2A, 3A, 4A, 5A, 10A
External shunt 50 / 60 / 75 mV10A, 15A, 20A, 30A, 40A, 50A, 60A, 100A, 150A, 200A, 250A, 300A, 400A, 500A, 600A, 800A, 1000A, 1500A, 2000A, 2500A, 3000A
DC voltageV0.5V, 1V, 5V, 10V, 25V, 50V, 100V, 250V, 500V, 600V

Source: factory catalogue p.3, 5. Other ranges and dual scales — ask us.

Drawings

Dimensions & drawings

CH120H / CH100HL back wiring diagram — M(+)/(−): load input; SOURCE: supply, AC 110 V or AC 220 V to suit the site; relay output: a = normally open, c = common, b = normally closed
CH120H / CH100HL back wiring diagram — M(+)/(−): load input; SOURCE: supply, AC 110 V or AC 220 V to suit the site; relay output: a = normally open, c = common, b = normally closed

Advantages

  • Limits are set directly on the dial — no menus or keypads
  • Reliable relay switching with a direct, at-a-glance reading
  • Shows the dynamic trend of the parameter, not just a number

Applications

  • Multi-station cold heading machines
  • Automatic testing equipment

Ask us

  • Panel cutout and dimension drawing for CH120H/HL
  • DC 24 V / DC 12 V supply versions
  • Samples and lead time — confirmed with each quote
  • Custom scale, dial text or pointer — see custom dials

Request a quote

Quote for CH120H / CH120HL

Tell us AC or DC, the range or CT / shunt ratio, any dial changes and the quantity. Attach a photo or drawing of the meter you replace if you have one.

More analog meter relays

Compare all
Request a QuoteWhatsApp