Square Panel Meters — 48, 72 & 96 mm

Square analog panel meters in traditional standard sizes, mainly used on high- and low-voltage switchgear. Choose by bezel size and panel cutout: the SQ series is a moving-iron design with selectable overload factor and interchangeable scale plates; the 81L16 / 89L2 / 6L2 / 42L6 square meters cover 48 to 120 mm bezels.

Square Panel Meters

2 series in this range

Specifications

Compare square panel meters

Values from our factory catalogue (p.16–19). “Ask us” = not in the catalogue yet — we confirm it with your quote.

ModelMeasuresAC / DCFront frame (mm)Panel cutout (mm)AccuracyExternal CT / PT / shuntAlarm relay
81L16 / 89L2 / 6L2 / 42L6Current, voltageAC48 / 72 / 80 / 120 squareSee drawingClass 1.5Ask us—
SQ48 / SQ72 / SQ96Current (1×–3× overload), voltageAC (moving iron)48 / 72 / 96 square45 / 68 / 91 squareClass 1.5 or 2.5CT x/5A · PT X/100–120V—

RSP square series

Specifications from catalogue p.17–18 — ask us for availability.

RSP ammeters (p.17)
ModelMeasuring rangeOverloadAccuracy
RSP-48A / RSP-72A / RSP-96A0–50 mA … 0–20 A / 0–30 A direct; with CT X/5A1× or 2×Class 1.5 or 2.5
RSP voltmeters (p.17)
ModelMeasuring rangeAccuracy
RSP-48V / RSP-72V / RSP-96V0–10 V … 0–600 V; with PT X/100VClass 1.5

Buying information

Ordering square panel meters

To quote, we need
Bezel size (48, 72, 96 mm or other), AC current or voltage, CT ratio (x/5A) or direct range, overload factor, and quantity.
Mixed models and ranges
List every model and range in one inquiry and we quote them together.
Minimum order, samples, lead time
MOQ 50 pcs per model; smaller quantities possible at a surcharge.
Samples and lead time: Ask us — confirmed in writing with each quote.
Dial and scale options
Overload factor 1×, 1.5×, 2× or 3× on SQ meters; interchangeable SQ scale plates; CT and PT ratio dials. Custom dials.

Manufacturing evidence

Made and documented in Ningbo

  • Analog meters made to Chinese national standard GB/T 7676-1998 (p.2).
  • Every meter is anti-static treated (p.2).
  • SQ48, SQ72, SQ96, 89L2, 6L2 and 42L6 are named on our UDEM LVD/EMC Attestation of Conformity No. M.2024.206.C99480.
  • Square meters mainly serve high- and low-voltage switchgear (p.16).
Standards & documents

Selection tips

Choosing the right model

Which cutout do I need?
SQ48 fits a 45×45 mm cutout, SQ72 a 68×68 mm cutout and SQ96 a 91×91 mm cutout.
What overload factor?
SQ current meters are 2× overload as standard. 1× (no overload), 1.5× or 3× can be made to order.
Changing the CT later?
On SQ AC ammeters the scale plate can be swapped for any CT with the same secondary current, with no loss of accuracy.
Full model selection guide

Request a quote

Request a Square Panel Meter Quote

Bezel size (48, 72, 96 mm or other), AC current or voltage, CT ratio (x/5A) or direct range, overload factor, and quantity.

FAQ

Frequently Asked Questions

What does “2× overload” mean on an SQ ammeter?

SQ current meters are made with 2× overload as standard; 1× (no overload), 1.5× and 3× versions can be made to order. The catalogue photo of an SQ48-10A shows its scale running to 20 A.

Are your square meters moving iron or moving coil?

The SQ48/72/96 are moving iron (electromagnetic). The 81L16 / 89L2 / 6L2 / 42L6 square meters are listed in the catalogue as moving coil.

Which square sizes do you make?

48, 72 and 96 mm (SQ series) and 48, 72, 80 and 120 mm (81L16, 89L2, 6L2, 42L6).

Where they are made

Workers assembling analog panel meters at benches with parts trays
Meter assembly benches
Glass-walled workshop corridor inside the factory
Workshop corridor
Labelled cartons on warehouse racking
Cartons on racking
Stock area with cartons along the workshop aisle
Stock area
Request a QuoteWhatsApp